The Steinel IR Quattro HD-2 24m COM1 is a ceiling infrared presence detector in a white, square 103 × 103 mm housing, built for flush mounting. Its detection field is square, 360°, divided into 5,200 switching zones. The COM1 version has one 230 V relay that switches the lighting on and off directly.
How much area it covers
Presence, meaning the small movements of someone seated at a desk, is detected over 9 × 9 m (81 m²). Movement towards the detector is covered over the same square, and movement across the field up to 24 × 24 m (576 m²). For room planning the first figure is the one that counts: above workstations the detectors are laid out on a 9 × 9 m grid.
The manufacturer specifies a mounting height of 2.5 to 10 m, with 2.8 m as the optimum. The four pyroelectric sensors can be damped or switched off individually, so the detector ignores a corridor or a door. Range is set with a potentiometer on the sensor module.
What it can switch
The relay handles 2,000 W of resistive or halogen load and 1,500 W of fluorescent lamps on electronic ballasts. With LED, the wattage of each lamp decides: up to 600 W for lamps above 8 W, 300 W for lamps of 2–8 W and only 100 W for lamps below 2 W. The detector also measures brightness and switches on only below a threshold set between 2 and 2,000 lx; the hold time runs from 5 s to 60 min.
Installation and set-up
The load module is fitted into the ceiling and screwed in, and the sensor module attaches to it magnetically. It connects to 220–240 V mains, so an electrician does the installation. An ordinary wall push-button can be wired to the push-button input (cable up to 50 m), which enables semi-automatic mode: light is switched on by hand and goes off by itself.
Settings are made in the STEINEL Connect app over Bluetooth Mesh, so a smartphone or tablet with Bluetooth is needed; no remote control is included. The same network links detectors into groups. This is the COM1 variant — it does not work with KNX or DALI, for which the manufacturer has separate versions. The detector is for indoor use (IP20) and operates from -20 to +50 °C: open-plan offices, classrooms, meeting rooms, halls and underground car parks.