A lighting plan for a renovation is a furnished floor plan marking every lighting point, switch and socket before the electrician cuts the first chase. A lamp is easy to change, but moving a lighting point after plastering means chasing, filler and repainting. Below you will find how many lighting points each room needs, the heights for wall lights and switches, the rules for downlights and LED strips, and a printable room-by-room checklist.

A lighting plan starts with the furniture, not the lamps. On the floor plan you mark the zones, a lighting point and a switch for each, and then agree circuits, heights and boxes with the electrician. Everything that goes into a wall or ceiling has to be known at first fix. Lamp models can wait; lamp types cannot.
Wiring is done in two stages. At first fix the electrician cuts chases, sets back boxes and pulls cables. Then come plaster, tiles and paint, and only at the end the second fix: switches, sockets and lamps. Any change after plastering means chasing and refinishing, and in a bathroom or kitchen often broken tiles too. Where and how chases may be cut in load-bearing walls and ceiling slabs is for a professional to decide.
The lamp type sets what must be in place before plastering. A heavy chandelier needs a solid fixing in the slab, and a downlight needs a certain void above a suspended ceiling. A wall light needs a box at the right height, and an LED strip needs a place for its power supply. So the order is: furniture layout and kitchen design → lighting plan → meeting with the electrician → plastering.
The electrician knows how to install everything safely and to the regulations, but not where your table will stand or which side of the bed you read on. This guide covers the second part. Always leave the work, the connections and the choice of protective devices to a qualified electrician.
The electrical plan for your lights is drawn on a scale floor plan, from the architect, the developer or your own hand. Draw the furniture in: table, sofa, TV, bed with bedside tables, desk and wardrobes. For the kitchen you need the finished cabinet design with wall-unit heights, because the worktop lighting depends on it.
For every room, answer three questions:
Think in layers: general (ceiling), task (worktop, table, armchair, mirror) and ambient (wall lights, floor lamps, accent lighting). Each layer gets its own switch, so the living-room door usually needs a double switch or two single ones. One-way, two-way and multi-gang models are in the Light switches category.
Mark on the plan with simple symbols: ceiling outlets, wall outlets with heights, switches (and what they control), switched sockets, sensors, LED strip runs with a place for the power supply. Then walk the home with the electrician and mark the points on the walls and ceiling. On paper you can be half a metre out; on the wall you see at once that the wall light lands behind the wardrobe.
Would you rather hand your lighting plan to someone who does this every day? Send us your furnished floor plan and we will help you choose the fittings and place them.
A living room of 15–25 m² needs 4–6 lighting points, a bedroom 3–5, and a living room open to the kitchen 7 or more. The number follows what you do in the room, not its area: every zone where you eat, read or work gets its own light.
A lighting point is a place a lamp shines from: an outlet in the ceiling or wall, a socket for a floor lamp or a run of LED strip. A track with several spotlights needs one outlet, even though it lights several areas. One lamp mid-ceiling gives flat light and dark corners, and in the evening it is either too much or too little. As a rough guide:
Illuminance and luminous flux are different quantities. You want about 100–150 lx of general light on the floor and furniture, and 300–500 lx on a worktop, a desk or at a reading chair (lux measures the light falling on a surface). For a first estimate of what to buy, count the flux of the light sources: about 150–250 lm/m² for all layers combined in a light-coloured interior, more with dark walls. The exact result depends on the fittings and the room, and wattage alone does not tell you how bright a lamp will be.
A lighting plan does not choose protective devices. Circuits, cable sizes and protection are designed by the electrician, in line with building regulations and the HD 60364 / IEC 60364 series of standards for low-voltage installations (BS 7671 in the UK). Your job is to say how you will use the light, so the split makes sense day to day.
In England and Wales, a new circuit, a new consumer unit or work within the zones of a bathroom is notifiable under Part P of the Building Regulations. A registered electrician can self-certify it; otherwise building control has to be told before the work starts.
Lighting and sockets go on separate circuits. That is standard practice: an overloaded socket circuit does not then put the lights out, and vice versa. Lighting itself is worth splitting into several circuits, for example by floor or by day and night zones, so that one tripped device does not darken the whole house. The stairs and hallways should not share a protective device with all the rooms.
In dwellings, HD 60364-4-41 calls for additional protection by an RCD with a rated residual current of no more than 30 mA for lighting circuits too. So that one trip does not switch everything off at once, the electrician spreads the circuits across several RCDs or uses combined devices (RCBOs). Ask how they will solve it.
Outdoor lighting gets its own circuit. The façade, paths and garden are damp places, and a fault outside should not put out the lights indoors. A separate circuit is also easy to run from a timer or dusk sensor in the consumer unit. A garage, workshop or outbuilding is usually supplied separately, especially when it stands away from the house.
In a bathroom, the zones in HD 60364-7-701 set the IP rating the fittings need: IPX7 in zone 0, at least IPX4 in zones 1 and 2, IPX5 where water jets are used. Zone boundaries depend on where the bath and shower are, so the electrician needs that before placing points.
A circuit is not a switch. One circuit can supply several independently switched groups: downlights along the wall, downlights over the table, wall lights. You decide how many groups to switch separately; the electrician decides how many circuits that becomes and how they are protected.
An outlet in the middle of the room only makes sense for a general light with nothing in particular beneath it. Over a table, an island, a bed or a sofa, the furniture decides where the outlet goes, not the shape of the room, so the outlet goes on the furniture’s axis.
A lighting outlet is a cable brought out of the ceiling or wall where a lamp will go. Typical layouts:
Two more details to settle with the team. A heavy chandelier needs a solid fixing in the slab; in a suspended ceiling it is usually independent of the boards, because the system’s load capacity is limited. Give the lamp’s weight to the electrician and the ceiling installer before the frame goes up. The second detail is precision: a canopy is usually 5–15 cm across, so an outlet placed “roughly” will show.
In a living room, hall or corridor, a wall-light outlet usually goes 160–180 cm above the finished floor, by the bed 100–120 cm and above a sofa 130–150 cm. Mark on the plan which point of the fitting you are dimensioning, usually its centre.
By the bed, the light sits roughly at the head height of someone sitting up in bed, just above the headboard. A tall headboard pushes it higher, so you need to know the bed before plastering. Above a sofa or armchair, the light should fall over your shoulder onto the book. Along long living-room and corridor walls, wall lights go about every 2 m. Other indicative heights:
Measure pairs of wall lights (by the bed, either side of the TV, fireplace or mirror) from the furniture axis, not the wall corner. With a double bed, each person needs their own reading-light switch within reach, on the fitting or in the wall by the bedside table. The ceiling light must also switch off without getting up, which means control from the door and from both sides of the bed.
In some wall lights the cable enters the backplate at the top or bottom, not the centre. If you have a model in mind, show it to the electrician, because the backplate must cover the box.
Recessed fittings need a plan before the ceiling frame goes up. Their position sets where the cables are left, and their depth sets how far the ceiling drops.
Agree groups of downlights with the electrician, for example general, along the walls and over the table. Each group is controlled separately, and how to wire that in a given system is the electrician’s call. If you plan dimming, decide now: you need dimmable lamps, an LED-compatible dimmer and often a deeper box. At each hole the electrician leaves spare cable so the fitting can come out for servicing. Downlights for suspended ceilings are in the Recessed Lights category.
A 12 or 24 V LED strip is not connected to the mains directly; a power supply (driver) sits between it and the 230 V installation. Planning a strip, you agree three things with the electrician: where the power supply will sit, how 230 V will reach it, and how far it is from there to the strip.
The power supply must stay accessible. It cannot be walled in or plastered over, because it warms up and will one day need replacing. Typical places are the top or inside of a kitchen wall unit, an access hatch in a suspended ceiling, a service niche or a wardrobe. It needs ventilation there and must come out without dismantling furniture. It is usually sized with about 20% power headroom.
The 12/24 V run should be short. At the same power, a 24 V strip draws half the current of a 12 V one, so the voltage drop is smaller. That is why 24 V is the usual choice for built-in work today. One feed point usually supplies up to about 5 m of strip, depending on its power per metre. Longer lines are fed from both ends or at several points, so cables must reach both ends before plastering. Cable size grows with the length of the run and the current, because extra-low voltage does not mean low current. The electrician chooses it.
Decide the control before plastering too: a wall switch, a touch or touchless switch under the cabinet, a dimmer or a remote. Dimming from a wall switch needs a dimmable power supply, and DALI control needs extra cable cores. Radio controllers need no control cable, but they need space for a receiver next to the power supply.
In a kitchen, an under-cabinet strip needs a 230 V outlet above or behind the wall units, where the kitchen designer expects it. For a ceiling with a cove or recess for the LED strip, decide which side the strip lies on and where the hatch for the power supply is. Stairs with strips in the treads and a sequential controller need a cable to every step and sensors at both ends of the flight, and none of that can be added afterwards. Power supplies for strips are in the LED power supplies category.
Switches most often go around 105–110 cm from the finished floor; older buildings sometimes have them higher. More and more people choose 90–110 cm, which also suits children and wheelchair users. More important than the figure is one height throughout the home, unless someone in the household needs switches lower or higher, for example a wheelchair user. A switch goes by the door on the handle side, usually 10–20 cm from the frame, not behind the door leaf. Tell the electrician the future floor build-up, because height is measured from the finished floor, not the screed.
Stairs, a long corridor, a bedroom with the bed far from the door and a living room with two entrances need control from several places. Two-way switches go at both ends, and for three or more places intermediate switches go in between. The alternatives are push buttons with a latching relay or wireless smart buttons. Each needs different wiring between boxes, so choose before plastering and let the electrician set the number of cores.
A plain mechanical switch needs no neutral to work, so the neutral often used to be left out of switch boxes. Most smart modules fitted in the box, many electronic dimmers and flush-mounted motion sensors need the N wire for their own supply. Ask the electrician to run it to every switch box: a detail now, chasing after plastering. Some devices work in a two-wire setup without N, but the choice is then much smaller.
Dimmers and modules need space a shallow box lacks. Wherever you may fit a dimmer, module or sensor, even years from now, ask for deep boxes (about 60 mm instead of the usual 40 mm or so). Check the dimensions of the specific module, because a deep box improves the odds without guaranteeing a fit. For multi-gang frames, check the box spacing (most often 71 mm) against the chosen switch range.
An LED dimmer must be designed for LED (most often trailing edge), and the lamps or drivers must be marked dimmable and compatible with the dimming method. You check this in their technical data. Watch the minimum load: a few 4–5 W downlights may not reach it. With smart control, choose a system that still works from the wall switch without the internet. LED-compatible dimmers are in the Dimmer switches category.
Floor and table lamps usually have a cord switch, so in the evening you walk round turning them on one by one. Sockets switched from a wall switch turn them all on with one press at the door.
In the living room, plan them by the corners of the sofa, by the reading chair, by the sideboard and behind the TV unit for backlighting behind the screen. In the bedroom they go by the bedside tables if you choose table lamps instead of wall lights, and in the hallway by a console table with a lamp.
Mark them with a different frame or a sticker, so that nobody plugs in a router or a charger that would go off with the lights. These are full sockets and socket rules apply. The electrician decides which circuit feeds them, how they are protected and which switch survives an accidentally plugged-in vacuum cleaner. If you end up short of switched sockets, app-controlled smart plugs are a stopgap, but a switch by the door is simpler for everyone.
A motion sensor needs its own box or outlet in a spot where it can see the way through the room, so it is placed together with the lamp outlets:
A ceiling sensor must not sit behind a pendant that blocks its view. Keep a manual option too, with a push button or switch nearby. PIR, microwave and twilight sensors are in the Motion Sensors category.
Outside, later changes cost most, because insulation, render, paving and lawn join the bill.
Outdoor connections need sealed connectors and boxes suited to the conditions: one kind for walls, another for the ground. IP68 alone does not make a part fit every use. Choosing and fitting them is the electrician’s job, and such parts are in the Electrical connectors and junction boxes category.
A home outlives its first furniture layout, so add three cheap reserves to today’s plan:
Before the chases are closed, photograph every wall and ceiling with a tape measure stretched out, horizontally from the corner and vertically from the floor. Number the photos by room and keep them with the floor plan. A short video walkthrough helps too.
When you hang shelves, curtain rails, a TV or kitchen units, you will know where the cables run. A good installation runs them vertically and horizontally from the boxes. Photos do not replace a cable detector before drilling, though, and you should never drill directly above, below or beside a box. When the work is done, ask the electrician for circuit labelling, a wiring diagram and the test certificate.
A lighting plan is easiest to budget around what cannot be postponed:
If the money does not stretch to everything, cut lamps, not outlets. A cheap lamp can be swapped at any time; a missing outlet means chasing.
Before plastering, an extra lighting point is mostly cable, a box and a little of the electrician’s time. Afterwards add chasing, filler, sanding and painting, and sometimes broken tiles. So a spare, capped outlet almost always pays off.
Plan types, not models: “pendant over the table”, “wall light by the bed”, “downlights over the worktop”. You need to choose the model before plastering only for trimless fittings, plaster-in LED profiles, recessed stair lights and wall lights with a small base.
For the plan itself, you only need the weight of the heaviest lamp (fixing), the depth of the recessed fittings (height of the suspended ceiling) and where the power supplies go.
Partly. A cable looped over a hook, an offset canopy or a track can cover a shift, usually up to about half a metre; how much depends on the cable length, the canopy size and the track length. In a suspended ceiling the electrician can usually reroute the cable in the void, but the old hole must be filled.
You do not have to buy it right away, but the installation is worth preparing: the N wire and deep boxes at the switches, empty conduits and space in the consumer unit. It costs little and later lets you fit modules without chasing.
A wall light frees up the bedside table and cannot be knocked over, but it needs an outlet at a fixed height and a decision about where the bed stands before plastering. A bedside lamp needs a socket by the bedside table, ideally a switched one. If the bed may still move, choose lamps and sockets.
The electrician assesses it: the cables (older buildings may have aluminium wiring and no protective conductor), the consumer unit and the protective devices. Only then do you know whether you add points or rewire completely, which changes how much chasing there will be.
Plan the functions: where the points should be, what switches on together and from where. The split into circuits, cable sizes, protective devices, cable routes and testing are the responsibility of a qualified electrician, and of a designer where an installation design is required. Safety depends on them.
This list is your lighting plan in tick-box form. Print it, take it to the meeting with your electrician and go through every room with it.